EN/07.2013/58/85
Parameters (SNMP address= 5)
(*): It means that the value is multiplied by 10. For example the value 102 is 10.2.
Parameter SNMP Address Trap message
(S001) Cooling set point 1 No
(S002) Second cooling set point 2 No
(S003) Heating set point 3 No
(S004) Second heater set point 4 No
(S005) Humidity set point 5 No
(S006) Cooling band 6 No
(S007) Heating band 7 No
(S008) Humidity band 8 No
(S009) Alarm limit low temperature 9 No
(S010) Hysteresis of low temperature alarm 10 No
(S011) Alarm limit high temperature 11 No
(S012) Hysteresis of high temperature alarm 12 No
(S013) Alarm limit max temperature 13 No
(S014) Hysteresis of max temperature alarm 14 No
(S015) Alarm limit low humidity 15 No
(S016) Alarm limit high humidity 16 No
(S017) Alarm delay (humidity - temperature) 17 No
(S018) Intrusion-vibration alarm delay 18 No
(S019) Limit supply temp in freecooling mode 19 No
(S020) Language selection 20 No
(S027) Password user 21 No
States (SNMP address= 6)
If the value is equal to 1, it means that the state is active.
State SNMP Address Trap message
Machine OFF 1 No
Machine ON 2 No
Manual testing 3 No
Machine in EMERGENCY 4 No
Machine in STANDBY 5 No
Automatic testing 6 No