Alarms (SNMP address= 7)
If the value is equal to 1, it means that the state is active.
The trap message will be sent when the alarm change its state.
Alarm SNMP Address Trap message
MAX TEMPERATURE 1 Ye s
HIGH TEMPERATURE 2 Ye s
LOW TEMPERATURE 3 Ye s
ANTIFREEZE 4 Ye s
LOW HUMIDITY 5 Ye s
HIGH HUMIDITY 6 Ye s
LOW PRESSURE 7 Ye s
HIGH PRESSURE 8 Ye s
AIR FLOW 9 Yes
FIRE - SMOKE 10 Ye s
INTRUSION - VIBRATION 11 Ye s
POWER FAILURE 12 Ye s
VOLTAGE OUT OF RANGE 13 Ye s
DIRTY FILTER 14 Ye s
COMPRESSOR THERMIC 15 Ye s
HEATER THERMIC 16 Ye s
EVAPORATOR FAN THERMIC 17 Ye s
CONDENSER FAN THERMIC 18 Ye s
LAN FAILURE 19 Yes
EVAPORATOR FAN1 BLOCKED 20 Ye s
EVAPORATOR FAN2 BLOCKED 21 Ye s
EVAPORATOR FAN3 BLOCKED 22 Ye s
EXTERNAL ENABLE ABSENT 23 Ye s
BAD WORKING 24 Ye s
FREE COOLING 25 Ye s
HUMIDITY SWITCH 26 Ye s
LEVEL 27 Ye s
BROKEN PROBE CH. IC1 28 Ye s
BROKEN PROBE CH. IC2 29 Ye s
BROKEN PROBE CH. IC3 30 Ye s
BROKEN PROBE CH. T1 31 Ye s
BROKEN PROBE CH. T2 32 Ye s
BROKEN PROBE CH. T3 33 Ye s
BROKEN PROBE CH. T4 34 Ye s
DIRTY FILTER 2 35 Ye s
TM OUT OF RANGE 36 Ye s
BROKEN AIR CONDITION 1 37 Ye s
BROKEN AIR CONDITION 2 38 Ye s
BROKEN AIR CONDITION 39 Ye s
WRONG PHASE 40 Ye s
DANFOSS COMPRESSOR COMMUNICATION ERROR 41 Ye s
VOLTAGE OUT OF RANGE 42 Ye s
TRIP LOCK 43 Ye s
DRIVE TEMPERATURE HIGH STATUS 44 Ye s
DISCHARGE TEMPERATURE HIGH STATUS 45 Ye s