15
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION
NOTE: When used as a vented heater, appliance must be installed only in a solid-fuel burning
replace with a working ue constructed of noncombustible material. You may use this heater
as a vented product. There are three reasons for operating your heater as a vented model:
1. The replace does not meet the clearance requirements for vent-free operation.
2. State or local codes do not permit vent-free operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you must permanently open chimney ue damp-
er. You must install the damper clamp accessory (provided). This will ensure vented operation
(see Fig. 9). The damper clamp will keep damper open.
See chart below for the minimum permanent ue opening you must provide. Attach
damper clamp so the minimum permanent opening will be maintained at all times.
Chimney Height (ft.) Minimum Permanent Flue Opening (sq. in)
6 ft to 15 ft 39 sq. in.
15 ft to 30 ft 29 sq. in.
Area of Various Standard Round Flues
Diameter (in.) Area (sq. in.)
5 in. 20 sq. in.
6 in. 29 sq. in.
7 in. 39 sq. in.
8 in. 51 sq. in.