48
PPaarraammeetteerr
RRaannggee
DDeeffaauulltt vvaalluuee
Battery Discharge SOC Lower
Limit(%)
0~99.9 5
SOC balancing
Enable/Disable Disable
SOC balancing power(%)
0~100 20
SOC Balance Control Mode Local Control Mode/Remote
Control Mode
Local Control
Mode
Protection Parameter->Battery Parameters
Battery overvoltage recovery
value(V)
2~1499.9 1450
Battery undervoltage recovery
value(V)
1~1499.8 550
Battery overvoltage level-1
protection value(V)
0.3~1500 1500
Battery overvoltage level-2
protection value(V)
0.3~1500 1500
Battery overvoltage level-3
protection value(V)
0.3~1500 1500
Battery undervoltage level-1
protection value(V)
0~1499.7 500
Battery undervoltage level-2
protection value(V)
0~1499.7 500
Battery undervoltage level-3
protection value(V)
0~1499.7 500
Battery overvoltage level-1
protection time(s)
0.02~300 1
Battery overvoltage level-2
protection time(s)
0.02~300 0.1
Battery overvoltage level-3
protection time(s)
0.02~300 0.1
Battery undervoltage level-1
protection time(s)
0.02~300 1
Battery undervoltage level-2
protection time(s)
0.02~300 0.1
7 iSolarCloud APP User Manual