49
PPaarraammeetteerr
RRaannggee
DDeeffaauulltt vvaalluuee
Battery undervoltage level-3
protection time(s)
0.02~300 0.1
Protection Parameter->PV Parameter
Bus-side overvoltage recovery
value(V)
0.2~1499.9 1450
Bus-side undervoltage recov-
ery value(V)
0.1~1499.8 550
Bus-side overvoltage level-1
protection value(V)*
0.3~1550 1500
Bus-side overvoltage level-2
protection value(V)
0.3~1550 1500
Bus-side overvoltage level-3
protection value(V)
0.3~1550 1500
Bus-side undervoltage level-1
protection value(V)*
0~1499.7 500
Bus-side undervoltage level-2
protection value(V)
0~1499.7 500
Bus-side undervoltage level-3
protection value(V)
0~1499.7 500
Bus-side overvoltage level-1
protection time(s)
0.02~300 1
Bus-side overvoltage level-2
protection time(s)
0.02~300 0.1
Bus-side overvoltage level-3
protection time(s)
0.02~300 0.1
Bus-side undervoltage level-1
protection time(s)
0.02~300 1
Bus-side undervoltage level-2
protection time(s)
0.02~300 0.1
Bus-side undervoltage level-3
protection time(s)
0.02~300 0.1
Charging & Discharging Man-
agement Parameter
User Manual 7 iSolarCloud APP