EasyManua.ls Logo

Sungrow SG500MX - Page 39

Sungrow SG500MX
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Manual 7 Parameters of LCD
33
Parameter Range Default
HVRT normal vol max(%) 110~120 110
HVRT tolera vol max (%) 120~140 130
Tmax-HVRT normal(ms) 100~20000 10000
Tmax-HVRT tolera(ms) 100~5000 500
Active Islanding Enable/Disable Disable
I leakage-pro(A) 1~8 5
Anti-PID mode Invalid/Suppression/Repair
Invalid (mode disabled)/
Suppression (mode
enabled)
Ins monitor measure time (S) 30/150/300/600 150
Ins monitor protect
threshold(K)
15~100 33
Note: * non-settable
Please refer to the LCD screen for the specific setting ranges of these parameters.

Table of Contents