User Manual 10 Operation of LCD Display
77
Parameter
Description
Default
Range
Fault slowup
Set the power rise rate
when a fault is
removed. W
hen it is
ON, the active power
raise rate can be set.
[ON] [OFF]/ [ON]
Slowup rate
Set the active power
raise rate.
100%/
min
8~100%/min
Save P-W Setting
Whether to save the
active power setting
[OFF] [OFF]/ [ON]
Save Q-Var
setting
Whether to save the
reactive power setting
[ON]
[Pt]/[Qt]/ [Off] /
[Q(P)] / [Q(U)]
Q-Var witch
Set the reactive power
regulation function
[OFF] [OFF]/ [ON]
PF
Inverter output power
factor
+1.000
-1.000~-0.800/
+0.800~+1.000
Q-Var limits
Inverter reactive power
limitation
0.0%
0~+100%/
0~-100%
Time
param
Standby time
Time from inverter
standby to startup
20s 20~255s
Recover time
Time from inverter fault
is removed to standby
30s
[IT: 300s]
0-900s
Derating param
Set the Derating param
to OFF or ON. If it is ON,
inverter will operate
with power derating
when grid frequency
exceeds the set value.
[OFF] [OFF]/ [ON]
Iso
param
ISO
Set the ISO protection
function to ON or OFF.
When it is ON, inverter
will not connect to the
grid when resistance to
the ground is below the
set value.
[ON] [OFF]/ [ON]
ISO pro value
Set the resistance to
the ground.
30 20~3000
LVRT param
Set the LVRT to OFF or
ON. W
hen it is ON,
inverter can keep
grid-
connection for a
certain time when grid
fault occurs and
provide reactive power
for grid recovery.
- [OFF]/ [ON]

Table of Contents

Other manuals for Sungrow SG80KTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG80KTL and is the answer not in the manual?

Sungrow SG80KTL Specifications

General IconGeneral
BrandSungrow
ModelSG80KTL
CategoryInverter
LanguageEnglish

Related product manuals