User Manual 10 Operation of LCD Display
81
10.10.4 Reactive Power Setting for Italy
If the “Countries” selected is “IT” (Italy), several LCD menus and operation methods
are different from other countries.
The differences focus on “Run-param” as shown below.
Italy “Q(P)” Mode
Power factor changes with the output power of the
inverter.
Select Q(P) mode and Press
to enter into the
“Run-para-Q(P)” sub-menu.
Press
to move the cursor; Press
to enter the
editing mode, then the selected parameter will be
shaded.
Press
to increase one-step value; Press
to
decrease one-step value.
Press ENTER to confirm the setting and exit from the
Run-param-Q(P) P3/3
Pf max 0.900
PA 020.0%
PB 050.0%
PC 100.0%
Uin 105.0%
Uout 100.0%
Tab. 10-8 Italy “Q(P)” Mode Parameters Explanation
PA*
Active power at point A (in %)
20% 20~100% 1%
PB*
Active power at point B (in %)
50% 20~100% 1%
PC*
Active power at point C (in %)
100% 20~100% 1%
Uin**
Enter Q(P) regulation mode
when grid voltage is above
Uin
105% 100~110% 1%
Uout**
Exit from the Q(P) regulation
mode when grid voltage is
below Uout
100% 90~100% 1%
*PA < PB≤ PC ** Uin>Uout