User Manual 10 Operation of LCD Display
81
10.10.4 Reactive Power Setting for Italy
If the Countries selected is “IT” (Italy), several LCD menus and operation methods
are different from other countries.
The differences focus on Run-param as shown below.
Italy Q(P) Mode
Power factor changes with the output power of the
inverter.
Select Q(P) mode and Press
to enter into the
Run-para-Q(P)sub-menu.
Press
to move the cursor; Press
to enter the
editing mode, then the selected parameter will be
shaded.
Press
to increase one-step value; Press
to
decrease one-step value.
Press ENTER to confirm the setting and exit from the
editing mode.
Run-param-Q(P) P3/3
Pf max 0.900
PA 020.0%
PB 050.0%
PC 100.0%
Uin 105.0%
Uout 100.0%
Tab. 10-8 Italy Q(P) Mode Parameters Explanation
Parameter
Explanation
Default
Range
Step
PA*
Active power at point A (in %)
20% 20~100% 1%
PB*
Active power at point B (in %)
50% 20~100% 1%
PC*
Active power at point C (in %)
100% 20~100% 1%
Pf max
Power factor at point C
0.9
0.9~1
0.01
Uin**
Enter Q(P) regulation mode
when grid voltage is above
Uin
105% 100~110% 1%
Uout**
Exit from the Q(P) regulation
mode when grid voltage is
below Uout
100% 90~100% 1%
*PA < PB PC ** UinUout

Table of Contents

Other manuals for Sungrow SG80KTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG80KTL and is the answer not in the manual?

Sungrow SG80KTL Specifications

General IconGeneral
BrandSungrow
ModelSG80KTL
CategoryInverter
LanguageEnglish

Related product manuals