EasyManua.ls Logo

Suntex PC-3100 - RS-485 Instruction set of set-up mode

Suntex PC-3100
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
9.3 RS-485 Instruction set of set-up mode:
Instruction format: ABBCC[(XXXX)] [(XXXX)] [(XXXX)]
A : Instruction leader character
BB : RS-485 ID
CC : Instruction
[] : Omission if there is no parameter
(XXXX): Parameter input
Readout of parameter settings in set-up mode
Items Instruction function
Syntactic
instruction
Output format
Data feedback
instances
1 Read ID #01ID ##0011IIDD >00 01
2 Read setting speed #01BR ##0011BBRR >00 9600
3
Read current output
Relative PH/ORP setting value
#01RS ##0011RRSS >00 4-20MA
4
Read current output
Relative temperature setting
value
#01TS ##0011TTSS >00 4-20MA
5
Read current output
Relative PH/ORP setting value
#01RA ##0011RRAA
>00 2.00pH
12.00pH
6
Read current output
Relative temperature setting
value
#01TA ##0011TTAA
>00 M 0.0C M
100.0C
7 Read cleaning setting value #01WT ##0011WWTT >00 0 0
8
Read high point alarm
controlling way
#01HM ##0011HHMM >00 AUTO
9
Read low point alarm controlling
way
#01LM ##0011LLMM >00 AUTO
10
Read high point alarm setting
value
#01HP ##0011HHPP
>00 10.00pH
0.10pH
11
Read low point alarm setting
value
#01LP ##0011LLPP
>00 4.00pH
0.10pH
12 Read measurement mode #01MM ##0011MMMM >00 pH
13
Read present temperature
compensation way
#01TM ##0011TTMM >00 MANUAL
14
Read present manual
temperature setting value or
automatic temperature correction
value
#01TV ##0011TTVV >00 M 25.0C

Table of Contents

Suntex PC-3100 - RS-485 Instruction set of set-up mode