Operation
72 NT 10000...NT 12000
During the SMTP tests an e-mail is sent to the e-mail address stored in the sys-
tem monitoring unit (active alerting). Before starting the test check whether
a valid e-mail address is stored under active alerting.
If no login is set up on the configured SMTP server, the password field must
be left empty. The login field is entered as the sender address for the e-mail.
If no login is specified, the Solar Inverter sends the e-mail as nt-inverter@sun-
ways.de.
Use the Send option to save the settings in the Solar Inverter.
Use Read to display the settings currently stored in the Solar Inverter.
Active alerting
General information With active alerting you can receive) status messages (errors and warnings) for
your solar system by e-mail. If a status message was active for longer than 15 mi-
nutes or occurred 5 times in one day, you will receive an e-mail at the next full
hour, which is sent to the e-mail address stored in the Solar Inverter.
NOTE
The main unit sends the status messages of all Solar Inverters if they are
CAN-networked.
Requirements:
The main unit must be connected to the Internet via a network or modem.
When dialling in via modem, the correct dial-up settings must be stored (see
Internet dial-up via modem).
Correct e-mail settings must be stored in the Sunways Browser (see E-mail
settings).
Alerting settings The alerting settings can be accessed with the button Settings – System Monito-
ring in the Active Alerting section.