5 : 59
Service
ModBus-register W3 applies to software after 0.76
Input Status Discrete Input (1 bit) Read only
Modbus Name Min/Max Remarks Default
1x0031 Radio chip broken 0/1 ALARM, requires HW reset
1x0032 Parameter file revision 0/1 ALARM, requires HW reset
1x0033 Parameter file format 0/1 ALARM, requires HW reset
1x0034 No ModBus ID 0/1 ALARM, requires HW reset
1x0035 No Application 0/1 ALARM, requires HW reset
1x0036 No parameters 0/1 ALARM, requires HW reset
1x0037 Parameter missing 0/1 ALARM, requires HW reset
1x0038 Parameter value error 0/1 ALARM, requires HW reset
1x0039 Parameter file size 0/1 ALARM, requires HW reset
1x0040 Wrong parameter file 0/1 ALARM, requires HW reset
1x0041 Check Duct Group SM 0/1 ALARM, resets after right parameters
1x0042 Check Duct Group DC 0/1 ALARM, resets after right parameters
1x0043 Previous parameters are lost 0/1 ALARM, requires HW reset
1x0044 Factory parameters take up 0/1 ALARM, requires HW reset
1x0045 Not used
1x0046 Not used
1x0047 No supply pressure from AHU 0/1 ALARM, resets automatically
1x0048 No exhaust pressure from AHU 0/1 ALARM, resets automatically
1x0049 Supply duct 100% open 0/1 ALARM, resets automatically
1x0050 Exhaust duct 100% open 0/1 ALARM, resets automatically
1x0051 Low voltage detect 0/1 ALARM, resets automatically
1x0052 Not used
1x0053 Duct group member missing 0/1 ALARM, resets automatically
1x0054 Negative pressure 0/1 ALARM, resets automatically