Application parameters W1
Application parameters are parameter-specific for the selected application.
Display image Description
P_1101 4
System1=H,2=C,3=ChOv,4=HC
min 1 max 4
Indicates how the climate
system should operate for
heating and cooling.
1 = Heating only
2 = Cooling only
3 = Change-over function
4 = Heating/Cooling
P_1102 1
0=ext.temp, 1 or 2 room units
min 0 max 2
Indicates whether one or
two room units are used. If 2
units are used they should be
connected with a cable.
0 = The controllers temp.
sensor is used, 1 = 1 unit
2 = 2 units
P_1103 10 C
Frost guard temp.
min 5 max 12
Indicates at which temperature
the frost protection should
switch in.
P_1108 1
Economy mode available
min 0 max 1
Indicates whether the Economy
mode is available.
0 = No
1 = Yes
P_1109 1
ActuatorCool 1=NC, 2=0-10V, 3=NO
min 1 max 3
Indicates which sort of valve
actuator is installed in the
cooling water circuit
(1=24V-NC, 2=0-10V, 3=24V-
NO)
P_1110 1
ActuatorHeat 1=NC, 2=0-10V, 3=NO
min 1 max 3
Indicates which sort of valve
actuator is installed in the
heating water circuit..
(1=24V-NC, 2=0-10V, 3=24V-
NC)
P_1111 0
Window 0=NP
min 0 max 0
Indicates whether a window
contact is installed and if so
how it is installed.
0 = No contact installed
P_1112 0
Occupancy 0=NP
min 0 max 0
Indicates whether a presence
detector is installed and if so
how it is installed.
0 = No contact installed
P_1113 5000
P term Change over
min 1 max 10000
Indicates the value for P for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
P_1114 50
I term Change over
min 1 max 10000
Indicates the value for I for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.