5 : 44
Service
Display image Description
P_1119 16 C
Room unit’s min temperature
min 0 max 20
Indicates which lowest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
P_1120 28 C
Room unit’s max temperature
min 25 max 50
Indicates which highest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
P_1121 20 C
Night cool temp set point
min 10 max 20
Indicates the temperature
setpoint applicable to the Night
cool function.
P_1122 480
RU back to auto state
min 0 max 1200
Indicates how long after the
most recent manual room
temperature adjustment that
the controller should return to
the AUTO mode.
0 = Not used
P_1123 3500
P term Cooling Scale 1:100
min 1 max 10000
Indicates the value for P for
cooling. A high value denotes
faster control. A low value
denotes slower control
P_1124 10
I term Cooling Scale 1:100
min 1 max 10000
Indicates the value for I for
cooling. A high value denotes
faster control. A low value
denotes slower control.
P_1125 3500
P term Heating Scale 1:100
min 1 max 10000
Indicates the value for P for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1126 10
I term Heating Scale 1:100
min 1 max 10000
Indicates the value for I for
heating. A high value denotes
faster control. A low value
denotes slower control.
P_1127 23
TC_Normal
min 15 max 30
Switch in cooling for normal
operation.
P_1128 21
TH_Normal
min 15 max 30
Switch in heating for normal
operation.
P_1129 25
TC_Economy
min 10 max 30
Switch in cooling for economic
operation
P_1130 19
TH_Economy
min 10 max 30
Switch in heating for economic
operation.