D200-100-01 16 I56-3888-010
APPENDIX C
EXAMPLE PIPE CONFIGURATIONS - 1 CHANNEL (can be duplicated for 2 channel units)
5.2
5.4
5.4
5.4
97m
End Hole
(Hole 18)
Hole 17Hole 16
HOLE
SIZE (mm)
1
2
2
2
3
2
4
2
56
2.5 2.5
789
2.5
10
2.5
FAN
SPEED
= 10
3
11 12 13
2.5
14
3
15
3
16
3
17
3.5 3.5 3.5
END
44
Example Pipe Configuration 1 Channel Single Pipe
100m x 18 Holes - Class C
Flow = 41 l/min, Balance = 0.65, Alarm Level = 1
Hole 2Hole 1
2.5
Hole 1
End hole
Hole 5
5
13
10
75m
(Hole 6)
Hole 2
Hole 3 Hole 4
HOLE
SIZE (mm)
1
3.5
2
3.5
3
4
4
4
5
5
END
5
80m - Class B
Flow: - 40 l/min, Balance = 0.73, Alarm level 1
13
13
13
13