D200-100-00
11
I56-3888-005
# PARAMETER PARAMETER RANGE
1 Channel
1 Sensor
1 Channel
2 Sensor
2 Channel
2 Sensor
44 Auxiliary relay set on flow fault YES/NO NO NO NO
45 Auxiliary relay set on sensor
communication fault
YES/NO NO NO NO
46 Auxiliary relay set on power restart
alert
YES/NO NO NO NO
47 Auxiliary relay is latched YES/NO NO NO NO
48 External input normal state OPEN, SHORT OPEN OPEN OPEN
49 External input triggers fault YES/NO NO NO NO
50 External input silences sounders YES/NO NO NO NO
51 External input reset device YES/NO YES YES YES
52 External input disables ASD YES/NO NO NO NO
53 External input ASD disabling time 1..1440 min 60 60 60
54 Pre-alarm delay 0 (OFF), 1..240 s 0 0 0
55 Pre-alarm and Alarm are in
cascade
YES, NO NO NO NO
58 Day start time HH:MI 08:00 08:00 08:00
59 Day end time HH:MI 17:00 17:00 17:00
60 Holiday day #1 date DD/MM empty empty empty
DD/MM empty empty empty
79 Holiday day #20 date DD/MM empty empty empty
80 Sounder activation mode On Pre-alarm, On Alarm Alarm Alarm Alarm
81 Day/night mode enabled YES/NO NO NO NO
82 Monday is holiday YES/NO NO NO NO
83 Tuesday is holiday YES/NO NO NO NO
84 Wednesday is holiday YES/NO NO NO NO
85 Thursday is holiday YES/NO NO NO NO
86 Friday is holiday YES/NO NO NO NO
87 Saturday is holiday YES/NO NO NO NO
88 Sunday is holiday YES/NO NO NO NO
89 Sensor 1 day alarm level 1..9 1 1 1
90 Sensor 2 day alarm level 1..9 1 1 1
91 Sensor 1 day pre-alarm level 1..9 1 1 1
92 Sensor 2 day pre-alarm level 1..9 1 1 1
93 Sensor 1 night alarm level 1..9 1 1 1
94 Sensor 2 night alarm level 1..9 1 1 1
95 Sensor 1 night pre-alarm level 1..9 1 1 1
96 Sensor 2 night pre-alarm level 1..9 1 1 1
97 Alarm mode Sensor alarm mode, module alarm
mode
X X X
98 Sensor communication timeout 0 (Disabled),1…240 s X X X
99 Remote output time for alarm 50, 100,...10000ms X X X

Other manuals for System Sensor FAAST LT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the System Sensor FAAST LT and is the answer not in the manual?

System Sensor FAAST LT Specifications

General IconGeneral
BrandSystem Sensor
ModelFAAST LT
CategorySmoke Alarm
LanguageEnglish

Related product manuals