# PARAMETER PARAMETER RANGE
1 Channel
1 Sensor
1 Channel
2 Sensor
2 Channel
2 Sensor
44 Auxiliary relay set on flow fault YES/NO NO NO NO
45 Auxiliary relay set on sensor
communication fault
YES/NO NO NO NO
46 Auxiliary relay set on power restart
alert
YES/NO NO NO NO
47 Auxiliary relay is latched YES/NO NO NO NO
48 External input normal state OPEN, SHORT OPEN OPEN OPEN
49 External input triggers fault YES/NO NO NO NO
50 External input silences sounders YES/NO NO NO NO
51 External input reset device YES/NO YES YES YES
52 External input disables ASD YES/NO NO NO NO
53 External input ASD disabling time 1..1440 min 60 60 60
54 Pre-alarm delay 0 (OFF), 1..240 s 0 0 0
55 Pre-alarm and Alarm are in
cascade
YES, NO NO NO NO
58 Day start time HH:MI 08:00 08:00 08:00
59 Day end time HH:MI 17:00 17:00 17:00
60 Holiday day #1 date DD/MM empty empty empty
… DD/MM empty empty empty
79 Holiday day #20 date DD/MM empty empty empty
80 Sounder activation mode On Pre-alarm, On Alarm Alarm Alarm Alarm
81 Day/night mode enabled YES/NO NO NO NO
82 Monday is holiday YES/NO NO NO NO
83 Tuesday is holiday YES/NO NO NO NO
84 Wednesday is holiday YES/NO NO NO NO
85 Thursday is holiday YES/NO NO NO NO
86 Friday is holiday YES/NO NO NO NO
87 Saturday is holiday YES/NO NO NO NO
88 Sunday is holiday YES/NO NO NO NO
89 Sensor 1 day alarm level 1..9 1 1 1
90 Sensor 2 day alarm level 1..9 1 1 1
91 Sensor 1 day pre-alarm level 1..9 1 1 1
92 Sensor 2 day pre-alarm level 1..9 1 1 1
93 Sensor 1 night alarm level 1..9 1 1 1
94 Sensor 2 night alarm level 1..9 1 1 1
95 Sensor 1 night pre-alarm level 1..9 1 1 1
96 Sensor 2 night pre-alarm level 1..9 1 1 1
97 Alarm mode Sensor alarm mode, module alarm
mode
98 Sensor communication timeout 0 (Disabled),1…240 s X X X
99 Remote output time for alarm 50, 100,...10000ms X X X