EasyManuals Logo

System Sensor FAAST LT User Manual

System Sensor FAAST LT
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
D200-100-00
16
I56-3888-005
APPENDIX C
EXAMPLE PIPE CONFIGURATIONS - 1 CHANNEL (can be duplicated for 2 channel units)
5
5.4
5.4
5.4
0.7
97.5m
End Hole
(Non-Sampling)
Hole 18Hole 17Hole 16
HOLE
SIZE (mm)
1
2
2
2
3
2
4
2
5
2
6
2.5 2.5
789
2.5
10
2.5
FAN
SPEED
= 10
2.5
11 12 13
2.5
14
3
15
3
16
3
17
3.5
18
3.5 3.5
END
44
Example Pipe Configuration 1 Channel Single Pipe
100m x 18 Holes - Class C
Hole 2Hole 1
2.5
Hole 1
End hole
Hole 5
FAN
SPEED
= 10
5
5
30
10
39
10
1
95m
(Hole 6)
Hole 2
Hole 3 Hole 4
HOLE
SIZE (mm)
1
3.5
2
3.5
3
4
4
4
5
5
END
5
Example Pipe Configuration 1 Channel Single Pipe
100m - Class B