# PARAMETER PARAMETER RANGE
1 Channel
1 Sensor
1 Channel
2 Sensor
2 Channel
2 Sensor
48 External input normal state OPEN, SHORT OPEN OPEN OPEN
49 External input triggers fault YES/NO NO NO NO
50 External input silences sounders YES/NO NO NO NO
51 External input reset device YES/NO YES YES YES
52 External input disables ASD YES/NO NO NO NO
53 External input ASD disabling time 1..1440 min 60 60 60
54 Pre-alarm delay 0 (OFF), 1..240 s X X X
55 Pre-alarm and Alarm are in
cascade
YES, NO X X X
58 Day start time HH:MI X X X
59 Day end time HH:MI X X X
60 Holiday day #1 date DD/MM X X X
… DD/MM X X X
79 Holiday day #20 date DD/MM X X X
80 Sounder activation mode On Pre-alarm, On Alarm X X X
81 Day/night mode enabled YES/NO X X X
82 Monday is holiday YES/NO X X X
83 Tuesday is holiday YES/NO X X X
84 Wednesday is holiday YES/NO X X X
85 Thursday is holiday YES/NO X X X
86 Friday is holiday YES/NO X X X
87 Saturday is holiday YES/NO X X X
88 Sunday is holiday YES/NO X X X
89 Sensor 1 day alarm level 1..9 X X X
90 Sensor 2 day alarm level 1..9 X X X
91 Sensor 1 day pre-alarm level 1..9 X X X
92 Sensor 2 day pre-alarm level 1..9 X X X
93 Sensor 1 night alarm level 1..9 X X X
94 Sensor 2 night alarm level 1..9 X X X
95 Sensor 1 night pre-alarm level 1..9 X X X
96 Sensor 2 night pre-alarm level 1..9 X X X
97 Alarm mode Sensor alarm mode, module alarm
mode
98 Sensor communication timeout 0 (Disabled),1…240 s 0 0 0
99 Remote output time for alarm 50, 100,...10000ms 3000 3000 3000