# PARAMETER
PARAMETER
RANGE
SA LB DESCRIPTION COMMENTS
41 Auxiliary relay set on
low/high temperature
alert
YES/NO
User chooses the event(s) that will
activate the auxiliary relay.
NO: not used
YES: activates the AUX relay
It is possible to have more than one
event set the Aux relay. If any one
of the chosen events occurs, the
Aux relay will be activated (they are
combined as an OR function).
42 Auxiliary relay set on
external input in not
normal state
YES/NO
43 Auxiliary relay set on
low power alert / high
power fault
YES/NO
44 Auxiliary relay set on
flow fault
YES/NO
45 Auxiliary relay set on
sensor communication
fault
YES/NO
46 Auxiliary relay set on
power restart alert
YES/NO
47 Auxiliary relay is
latched
YES/NO
NO: The AUX relay is activated when a
chosen event is present and will reset
when the event trigger is removed.
YES: The general AUX relay is activated
when a chosen event is present. When
the event trigger is removed the relay
remains set until a device reset.
48 External input normal
state
OPEN, SHORT
No action is triggered by the input in this
state.
OPEN: requires closed contacts to cause
an input response.
SHORT: requires an open circuit to cause
an input response.
49 External input triggers
fault
YES/NO
User chooses the activity that is triggered
by the external input.
NO: not used
YES: activated by external input.
Note that only one action can be selected
at a time.
Note: External input only active in
NORMAL state.
50 External input silences
sounders
YES/NO
51 External input resets
device
YES/NO
52 External input disables
device
YES/NO
53 External input disabling
time
1..1440 min
When the external input is used to disable
the device, this option sets the disable
period.
54 Pre-alarm delay 0 (OFF), 1..240 s
A delay can be set to stop reporting a pre-
alarm condition for a defined period.
If the pre-alarm condition is removed
before activation of the pre-alarm is
reported, the delay will be reset.
55 Pre-alarm and Alarm
are in cascade
YES, NO
NO: Alarm (or alarm delay) will activate
immediately on alarm condition.
YES: Alarm condition does not activate
until pre-alarm condition (and related
delay) has completed.
58 Day start time HH:MI
Start of daytime mode operation Minimum daytime period = 1 hour.
59 Day end time HH:MI
End of daytime mode operation
60 Holiday day #1 date DD/MM
On these days, the device uses the night
time settings only (every year).
00/00 = not used
Day/Night mode (Parameter 81)
must be set to YES.
Holidays #2…#19 DD/MM
79 Holiday day #20 date DD/MM
80 Sounder activation
mode
On Pre-alarm, On
Alarm
This option defines which event will
activate the sounder relay.
If “On Pre-Alarm” is selected,
sounders remain active in alarm.
81 Day/night mode
enabled
YES/NO
Allows use of two different sets of alarm
and pre-alarm levels.
NO: Day settings are always used
YES: Device will change between day and
night settings at selected times.