Annex๎˜ƒ10โ€”3๎˜ƒ
๎˜ƒ
10.7๎˜ƒMenu๎˜ƒโ€“๎˜ƒdrawing๎˜ƒof๎˜ƒthe๎˜ƒmenu๎˜ƒto๎˜ƒguide๎˜ƒthe๎˜ƒuser๎˜ƒ
Drawing๎˜ƒof๎˜ƒthe๎˜ƒmenu๎˜ƒappears๎˜ƒfrom๎˜ƒsection๎˜ƒ12๎˜ƒ
10.8๎˜ƒThe๎˜ƒstart๎˜ƒdispla y๎˜ƒ
The๎˜ƒstart๎˜ƒpicture๎˜ƒshown๎˜ƒwhen๎˜ƒthe๎˜ƒpotentiometer๎˜ƒhas๎˜ƒnot๎˜ƒbeen๎˜ƒactivated๎˜ƒfor๎˜ƒ10๎˜ƒminutes๎˜ƒ
๏‚ท In:๎˜ƒnnn%๎˜ƒshows๎˜ƒthe๎˜ƒcapacity๎˜ƒordered๎˜ƒby๎˜ƒthe๎˜ƒmain๎˜ƒair๎˜ƒhandling๎˜ƒunit๎˜ƒcontroller.๎˜ƒ
๏‚ท Out:๎˜ƒnnn%๎˜ƒshows๎˜ƒthe๎˜ƒcapacity๎˜ƒordered๎˜ƒby๎˜ƒthis๎˜ƒinternal๎˜ƒcontroller๎˜ƒโ€๎˜ƒLMC251๎˜ƒโ€“๎˜ƒof๎˜ƒthe๎˜ƒcompressor.๎˜ƒ
10.9๎˜ƒSettings๎˜ƒ
About๎˜ƒbasic๎˜ƒsettings๎˜ƒin๎˜ƒthe๎˜ƒsubmenus๎˜ƒin๎˜ƒthe๎˜ƒLMC251๎˜ƒ
10.10๎˜ƒAutomatic๎˜ƒresets๎˜ƒof๎˜ƒthe๎˜ƒhigh๎˜ƒpressure ๎˜ƒswitch๎˜ƒ
This๎˜ƒis๎˜ƒabout๎˜ƒthe๎˜ƒmaximum๎˜ƒnumber๎˜ƒof๎˜ƒautomatic๎˜ƒresets๎˜ƒof๎˜ƒthe๎˜ƒhigh๎˜ƒpressure๎˜ƒswitch๎˜ƒthat๎˜ƒare๎˜ƒacceptable๎˜ƒ
within๎˜ƒone๎˜ƒhour.๎˜ƒ๎˜ƒIf๎˜ƒthis๎˜ƒnumber๎˜ƒis๎˜ƒexceeded,๎˜ƒthe๎˜ƒunit๎˜ƒwill๎˜ƒbe๎˜ƒshut๎˜ƒdown๎˜ƒuntil๎˜ƒthe๎˜ƒhigh๎˜ƒpressure๎˜ƒswitch๎˜ƒhas๎˜ƒ
been๎˜ƒreset๎˜ƒmanually.๎˜ƒ
10.11๎˜ƒPolarity๎˜ƒ
The๎˜ƒAlarm๎˜ƒpolarity๎˜ƒcan๎˜ƒbe๎˜ƒset๎˜ƒtoโ€Normally๎˜ƒOpenโ€ ๎˜ƒor๎˜ƒโ€Normally๎˜ƒClosedโ€.๎˜ƒ
10.12๎˜ƒHotgas๎˜ƒโ€“๎˜ƒsetting๎˜ƒof๎˜ƒperiod๎˜ƒ
This๎˜ƒis๎˜ƒthe๎˜ƒnumber๎˜ƒof๎˜ƒseconds๎˜ƒthat๎˜ƒthe๎˜ƒhotgas๎˜ƒvalve๎˜ƒis๎˜ƒopen.๎˜ƒThe๎˜ƒperiod๎˜ƒis๎˜ƒrelatively๎˜ƒlong,๎˜ƒbut๎˜ƒthe๎˜ƒsupply๎˜ƒ
temperature๎˜ƒis๎˜ƒnot๎˜ƒoscillating๎˜ƒat๎˜ƒall๎˜ƒand๎˜ƒthe๎˜ƒstability๎˜ƒof๎˜ƒthe๎˜ƒsupply๎˜ƒtemperature๎˜ƒis๎˜ƒsufficient.๎˜ƒThe๎˜ƒnumber๎˜ƒof๎˜ƒ
seconds๎˜ƒis๎˜ƒa๎˜ƒfactory๎˜ƒsetting๎˜ƒthat๎˜ƒshould๎˜ƒnot๎˜ƒbe๎˜ƒreduced.๎˜ƒReduction๎˜ƒof๎˜ƒthe
๎˜ƒnumber๎˜ƒof๎˜ƒseconds๎˜ƒwill๎˜ƒnot๎˜ƒ
improve๎˜ƒthe๎˜ƒstability๎˜ƒof๎˜ƒthe๎˜ƒtemperature๎˜ƒto๎˜ƒa๎˜ƒdegree๎˜ƒthat๎˜ƒcan๎˜ƒbe๎˜ƒproven๎˜ƒby๎˜ƒmeasurements.๎˜ƒIf๎˜ƒthe๎˜ƒnumber๎˜ƒ
of๎˜ƒseconds๎˜ƒis๎˜ƒreduced,๎˜ƒthe๎˜ƒnumber๎˜ƒof๎˜ƒtimes๎˜ƒthat๎˜ƒthe๎˜ƒvalve๎˜ƒis๎˜ƒopened๎˜ƒand๎˜ƒclosed๎˜ƒwill๎˜ƒbe๎˜ƒincreased๎˜ƒโ€“๎˜ƒmaybe๎˜ƒ
considerably,๎˜ƒand๎˜ƒthe๎˜ƒvalve๎˜ƒcould๎˜ƒbe๎˜ƒworn๎˜ƒ
out๎˜ƒprematurely.๎˜ƒ๎˜ƒ
10.13๎˜ƒLimiter๎˜ƒ
DeltaMax๎˜ƒis๎˜ƒthe๎˜ƒmaximum๎˜ƒacceptable๎˜ƒchange๎˜ƒin๎˜ƒ%๎˜ƒ/๎˜ƒsecond๎˜ƒof๎˜ƒthe๎˜ƒactual๎˜ƒcooling๎˜ƒcapacity.๎˜ƒ
10.14๎˜ƒService๎˜ƒ
In๎˜ƒthis๎˜ƒmenu๎˜ƒinformation๎˜ƒabout๎˜ƒthe๎˜ƒsoftware๎˜ƒversion๎˜ƒin๎˜ƒthe๎˜ƒcontroller๎˜ƒas๎˜ƒwell๎˜ƒas๎˜ƒ2๎˜ƒsubmenus๎˜ƒโ€“๎˜ƒโ€œManual๎˜ƒ
operationโ€๎˜ƒand๎˜ƒโ€œRuntimeโ€๎˜ƒ
10.15๎˜ƒManual๎˜ƒoperation๎˜ƒ
When๎˜ƒthe๎˜ƒmenu๎˜ƒโ€“๎˜ƒManual๎˜ƒoperation๎˜ƒโ€๎˜ƒis๎˜ƒactivated,๎˜ƒthe๎˜ƒtechnician๎˜ƒis๎˜ƒable๎˜ƒto๎˜ƒcontrol๎˜ƒthe๎˜ƒoperation๎˜ƒmanually,๎˜ƒ
when๎˜ƒthe๎˜ƒstart๎˜ƒsignal๎˜ƒfrom๎˜ƒthe๎˜ƒmain๎˜ƒair๎˜ƒhandling๎˜ƒunit๎˜ƒcontroller๎˜ƒis๎˜ƒon๎˜ƒ(start๎˜ƒsignal๎˜ƒis๎˜ƒjust๎˜ƒpotential๎˜ƒfree๎˜ƒ
connection๎˜ƒof๎˜ƒthe๎˜ƒtwo๎˜ƒterminals๎˜ƒโ€“๎˜ƒ3&4).๎˜ƒThis๎˜ƒprocedure๎˜ƒis๎˜ƒrelevant๎˜ƒfor๎˜ƒthe๎˜ƒtest๎˜ƒduring
๎˜ƒthe๎˜ƒannual๎˜ƒ
maintenance๎˜ƒwith๎˜ƒthe๎˜ƒcontrol๎˜ƒof๎˜ƒall๎˜ƒsafety๎˜ƒand๎˜ƒregulation๎˜ƒprocedures๎˜ƒor๎˜ƒafter๎˜ƒinstallation๎˜ƒof๎˜ƒnew๎˜ƒ
components.๎˜ƒ
If๎˜ƒno๎˜ƒnew๎˜ƒsettings๎˜ƒhave๎˜ƒbeen๎˜ƒcarried๎˜ƒout๎˜ƒon๎˜ƒthe๎˜ƒcontroller๎˜ƒfor๎˜ƒ10๎˜ƒminutes,๎˜ƒthe๎˜ƒmenu๎˜ƒโ€“๎˜ƒManual๎˜ƒoperation๎˜ƒโ€“๎˜ƒ
is๎˜ƒdeactivated,๎˜ƒand๎˜ƒthe๎˜ƒunit๎˜ƒreturns๎˜ƒto๎˜ƒthe๎˜ƒautomatic๎˜ƒmode.๎˜ƒ
10.16๎˜ƒRunning๎˜ƒhours๎˜ƒand๎˜ƒhotgas๎˜ƒactivations๎˜ƒ
In๎˜ƒthis๎˜ƒmenu๎˜ƒthe๎˜ƒnumber๎˜ƒof๎˜ƒrunning๎˜ƒhours๎˜ƒfor๎˜ƒthe๎˜ƒcompressor,๎˜ƒand๎˜ƒthe๎˜ƒnumber๎˜ƒof๎˜ƒactivations๎˜ƒof๎˜ƒthe๎˜ƒhotgas๎˜ƒ
valve๎˜ƒcan๎˜ƒbe๎˜ƒread.๎˜ƒThis๎˜ƒinformation๎˜ƒis๎˜ƒvaluable๎˜ƒfor๎˜ƒthe๎˜ƒmaintenance.๎˜ƒ
10.17๎˜ƒAlarm๎˜ƒ
10.17.1๎˜ƒAlarm๎˜ƒ
Show๎˜ƒthe๎˜ƒactual๎˜ƒalarm๎˜ƒwith๎˜ƒalarm๎˜ƒnumber.๎˜ƒ