Annex12—2
12.2SetupforDanfossFC101forDVunitswithACmotors
SETUPISDONEINFACTORYBEFOREDELIVERY
ToreloadSystemairfactorys ettingsfromthecontrolpanel:
050:LCPCopy: [2]
SystemairfactorysetupisbasedonDanfossinitialization.
1422:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactorysetup:
001:Languageselection:
103:Torquecharacteristic: Singlefan:[3]AutoEnergyoptim.
Withtwinfansetup:[1]VariableTorque
120:MotorPower: Accordingtomotorplate/orderpapers
Withtwinfansetuptotalpowermustbeused
124:MotorCurrent: Accordingtomotorplate
/orderpapers
Withtwinfansetuptotalcurrentmustbeused
125:MotorNominalSpeed: Accordingtomotorplate/or derpapers
142:MotorCableLength: 3m
150:MotorMagnetisationatzerospeed.: 0%
152:Min.SpeedNormalMagnetisation: 10Hz
173:
FlyingStart: [0]Disabled
190:MotorThermalProtection: [2]Thermistortrip
315:Reference1Source: [2]AnaloginputAI54
193:ThermistorSource: [1]AnaloginputAI53
303:MaximumReference: Max.Hzfromorderpapers
316+317:Reference2‐and3Source: [0]Nofunction
341+342:Ramp1upanddown: 20Sec.
419:Max.OutputFrequency: 90Hz
414:MotorSpeedHighLimit:90Hz
418:Currentlimit: 100%
512:Terminal27Digitalinput:[0]Nooperation
540.0:FunctionRelay: [3]Driveready/remote
540.1:FunctionRelay:
[3]Driveready/remote
625:Terminal54HighReference: Max.Hzfromorderpapers
1403:Overmodulation: [1]Active
1420:ResetMode: [2]Automaticresetx2
050:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)
Connections:
010V: terminal5455
Start: terminal1218
Thermistor: terminal5053
Driveready: terminal12