EasyManua.ls Logo

SystemAir Danvent TIME - AC-Fan Operation Without Thermistor For Danfoss Fc101

SystemAir Danvent TIME
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Annex12—4
12.3AC‐fanoperationwithout thermistorforDanfossFC101.
Systemairfactoryset‐upisbasedonDanfossinitialization.
14‐22:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactoryset‐up:
0‐01:Languageselection:
1‐03:Torquecharacteristic:
 [3]Auto‐Energyoptim.
1‐20:Motorpower: Accordingtomotorplate
1‐24:MotorCurrent: Accordingtomotorplate
1‐25:MotorNominalSpeed: Accordingtomotorplate
1‐29:Automaticmotoradption(AMA): [1]Kompl.motoradaptionto(Turnpoweroffandon.)
1‐42:MotorCableLeng th:
Orderspecific
1‐50:
MotorMagnetisationatzerospeed.: 0%
1‐52:Min.SpeedNormalMagnetisation: 10Hz
1‐73:Flyingstart:  [0]Deaktivated
5‐40.0:FunctionRelay: [3]Driveready/remote
14‐03:Overmodulation: [1]Active
14‐20:ResetMode: [2]Automaticresetx2
0‐50:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)
Connections:
0‐10V: terminal54‐55
Start: terminal12‐18
Driveready: terminal1‐2
Jumper terminal12‐27

Table of Contents