EasyManua.ls Logo

SystemAir Danvent TIME - Set-Up Danfoss Fc101 For DV-Units With Pm Motors

SystemAir Danvent TIME
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Annex12—5
12.4Set‐upDanfossFC101forDV‐unitswithPMmotors
SETUPISDONEINFACTORYBEFOREDELIVERY
ToreloadSystemairfactorysettingsfromthecontrolpanel:
0‐50:LCPCopy: [2]
Systemairfactoryset‐upisbasedonDanfossinitialization.
14‐22:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactoryset‐up:
0‐01:Languageselection:
1‐06:ClockwiseDirection: [1]Inverse
1‐10:MotorConstruction: [1]PM,non‐salientSPM
1‐24:MotorCurrent: Accordingtomotorplate/Schedule
1‐25:MotorNominalSpeed:Accordingtomotorplate/Schedule
1‐26:MotorCont.Ratedtorque: Accordingtomotorplate/
Schedule
1‐30:StatorResistance(Rs): Accordingtomotorplate/ Schedule
1‐37:d‐axisinductance(Ld): Accordingtomotorplate/Schedule
1‐39:MotorPoles: Accordingtomotorplate/Schedule
1‐40:BackEMFat1000RPM: Accordingtomotorplate/Schedule
1‐42:Motor
CableLength: 3m
1‐90:MotorThermalProtection: [2]Thermistortrip
3‐15:Reference1Source: [2]AnaloginputAI54
1‐93:ThermistorSource: [1]AnaloginputAI53
3‐03:MaximumReference: Accordingtomotorplate/Schedule
3‐16+3‐17:Reference2‐and3Source: [0]Nofunction
3‐41+3‐42:Ramp1Upanddown: 30sec.
4‐19:Max.OutputFrequency: Accordingtomotorplate/Schedule
4‐14:MotorSpeedHighLimit: Accordingtomotorplate/Schedule
4‐18:Currentlimit: 115%
5‐12:Terminal27Digitalinput: [0]Nooperation
5‐40.0:FunctionRelay: [3]Driveready/remote
5‐40.1:FunctionRelay: [3]Driveready/remote
6‐25:Terminal54HighReference: Accordingtomotorplate/Schedule
14‐03:Overmodulation: [1]Active
14‐20:ResetMode: [2]Automaticresetx2
0‐50:LCPCopy: [1]AlltoLCP(Copyof
Systemairfactorysettingstopanel)
Connections:
0‐10V: terminal54‐55
Start: terminal12‐18
Thermistor: terminal50‐53
Driveready: terminal1‐2

Table of Contents