MenuLevel1MenuLevel2MenuLevel3Explanation
Functions
Analogoutput
Analogoutput
A01auto/man/off
A02auto/man/off
A03auto/man/off
Showscurrentanalogue
outputsin0–10Vtohot/cold
wateractuatororelectrical
re-heaterandrotordrive/
bypassdamper.
SetAO1(Analogueoutput
tohotwateractuatoror
electricalre-heater)toauto,
manoroff.
Defaultvalue:auto.
SetAO2(Analogueoutputto
coldwateractuator)toauto,
manoroff.
Defaultvalue:auto.
SetAO3(Analogueoutputto
rotordriveorbypassdamper)
toautoorman.Defaultis
auto.Selectingmanenables
theusertomanuallycontrol
theactuator/damperwitha
0–10Vsignal.0Vcompletely
closedand10Vcompletely
openedactuator/bypass
damper.
Functions
Digitalinput
Digitalinput
DI1ON/OFF
DI2ON/OFF
DI3ON/OFF
DI4ON/OFF
DI5ON/OFF
DI6ON/OFF
DI7ON/OFF
Showscurrentstatusofthe
digitalinputsONorOFF
DI1:Fanconguration
DI2:Fanconguration
DI3:Fanconguration
DI4:Heaterdeactivated
DI5:Extended/forcedrunning
DI6forrotatingheat
exchanger:
Rotorsensor
DI6forcounterowheat
exchanger:
Bypassdamperlimitswitch
DI7:Home/leave
SAVEVTR200/BInstallationandService