MenuLevel1MenuLevel2MenuLevel3Explanation
Demandcontrol
DemandcontrolCO2/
RH
Setpoint0ppm/0%RH
P-Band100ppm/10%RH
I-TimeOFF
Itispossiblecontrolthe
indoorairqualityusing
RH(Relativehumidity)
orCO2(Carbondioxide)
sensor/sensors.Default
setpointsettingisOff.
(0%/0ppm).
Bothtypesshouldbeable
touseatthesametime,
meaning2PIcontrollers.
Whendemandcontrol
setpointiscongured,fans
settoautomodeandregulate
againstthesetpoint.The
fansymbolshouldhavethe
middleareaempty,andthe
outerandinnerlled.It
shouldnotbepossibleto
changeeither.
Fancontrol
Airflow
Airflow
%
Nom
High
Low
EF
50
100
25
SF
50
100
25
Usethisdialogueframetoset
theairowin%.Theairow
canbesetindividuallyfor
eachfan
EF:Extractfan,
SF:Supplyfan
SettheairowforEFandSF
foreachstep(Low,Nom,and
High.
Functions
Manualfanstop
Manualfanstop
Allowmanualfan
stopY/N
Setifitshouldbepossible
toturnoffthefansintheunit
manuallyfromthecontrol
panel.
ChosebetweenYandN.
IfYisselectedthefanscan
beturnedoffbyturningthe
SELECTIONknobtoempty
fan
Functions
Analoginput
Analoginput
1:SS20.0
2:ETS23.0
3:Unused/PHS
4:Unused/OT/FPS
20.0
5:OS10.5
6:RH0%
Showsanalogueinputsfrom
activetemperaturesensors.
SS:Supplyairtempsensor.
ETS:Extractairtempsensor.
PHS:Preheatersensor.
FPS:Frostprotectionsensor.
OS:Outdoorairtempsensor.
OT:Overheatprotection
sensor.
RH:Relativehumiditysensor.