MenuLevel1MenuLevel2MenuLevel3Explanation
Functions
ExternalDI
ExternalDI
ActiveWireless:
DI1/..DI20
Assignto:
—/DI-5/DI7
ExternalDImenuonly
availableifoneorseveral
“Inputmodules”areboundto
thesystem.Activewireless
DI1-20isdependedonactual
nodefor“Inputmodule”.
Nodeshownin“Wireless”
menuwhichnode
representingDImodule
inputs.
Eg.
Node1type:DI.Active
wirelessDI1andDI2
Node2type:DI.Active
wirelessDI3andDI4
Node10type:DI.Active
wirelessDI19andDI20
ActivewirelessDI1-20are
availabletoassigntoDI1-5
andDI7forthesysteminthe
airhandlingunit.
DI6isnotavailableas
selection,usedbythesystem
intheairhandlingunit.
UnsignedDIisshownas
(none).
Toresetapreviously
assignedDI,select“–”
andconrmtheselection.
Functions
Wireless
ExternalDI
Note:1Type:None
State:NoNetwork
Data:0
Wirelesssystemstatus.
Node:Showsnumberof
boundwirelessmodule.
Type:None/UI:User
Interface(Controlpanel)/DI:
DigitalInputmodule/CO2:
CO2sensormodule/RH:RH
sensormodule.
State:NoNetwork:No
gatewayconnectedtothe
systemforairhandling
unit/Unbound:Nobonded
module/OK:Successful
bindingofmodule
Data:Theactualvalue
frommodule/Commfail:
Communicationfailure,se
manualforactualmodulefor
troubleshooting.
Toresetallboundnodes,
seeusermanualforGateway
Wireless.
SAVEVTR200/BInstallationandService
208061
31