- 38 -
APPLICATIONS
Space Heating Applications
WARNING
Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol group
must not be introduced into the system when used for open loop potable water and
space heating.
The T-K3/T-K3-Pro can be used to supply potable water and space heating and shall
not be connected to any heating system or component(s) previously used with non-
potable water where any chemicals were added to the water heating appliances.
When the system requires water for space heating at temperatures higher than required
for other uses, a means such as a mixing valve shall be installed to temper the water for
those other uses in order to reduce scald hazard potential.
Water temperature over 125 °F can cause severe burns instantly or death from scalds.
Chemicals such as diluted Glycol can be used for radiant floor, Hydro/fan coil air or
Baseboard heating only. The diluted solution of glycol must contain LESS than 30% of
Glycol. Be aware that in closed-loop glycol systems, low pressure in the heat exchanger
can cause low-temperature boiling, resulting in excessive noise and damage to the
water heater. Consult with the glycol maker for specifications prior to use.
Re-circulation:
This is a concept drawing only.
* Size the pump to provide at about
2
GPM through the
system at 15 Ft of Head plus applications and piping head
losses. 2 GPM will allow the system to operate at its
optimal performance.
* If the application requires a higher re-circulating flow rate,
make sure that the re-circulating flow rate is no greater
than 4 GPM. If the flow rate is too high, the system could
be damaged by erosion

Other manuals for Takagi T-K3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Takagi T-K3 and is the answer not in the manual?

Takagi T-K3 Specifications

General IconGeneral
TypeTankless
Installation TypeIndoor
Maximum BTU Input199, 000 BTU/h
Gas Connection Size3/4"
Vent Size3"
Hot Water Flow Rate (at 35°C rise)6.6 GPM
Maximum Input199, 000 BTU/h

Related product manuals