MPPT charge controller User Manual
Table 6-1 Battery charging voltage
Battery type Average voltage Float voltage Charging ratio
GEL/OPzV 14.1V 13.6V 0.15C
AGM 14.4V 13.5V 0.15C
Lead-Carbon 14.1V 13.5V 0.20C
Flooded 14.7V 13.5V 0.15C
Customerize 14.2V(24V) 13.5V 0.20C
13.5V(48V) 13.3V 0.20C
Traction 15.2V 13.5V 0.15C
OPzS 14.7V 13.4V 0.15C
5
5
.6 User Config
.6 User Config
Users can realize the rapid configuration of the system according to requirements. The following
submenus are included under this interface.
>Screen Set
Date & Time
>Trigger
Command
>User Config
>Screen Set
Display Setting range Description
Backlight_KeepOn
1-Enable;0-Disable
Default setting:0-Disable
Constant backlight
enablement.
Page_Turn_Auto
3~30s
Default setting:5s
Automatic page turning time
of real-time information
display interface;3~30s can
be set, and the page will
automatically turn after
timeout.
>Data & Time From this page, you can set the current time.
>Trigger
Command
Display Description
Mute control Keep buzzer silent for one time.