MPPT charge controller User Manual
6. FAQ
6.1 Fault code
Alarm level definition:
Fault: MPPT charger failure, into shutdown mode, no more charging.
Warning: MPPT charger warning, but also charging normally.
Type ID Name Reason Suggestion
Fault
0 Vbus_OV PV voltage is too high.
Check the string of PV
array.
Make sure that the PV open
circuit voltage never higher
than the maximum range of
MPPT charger.
If it happens frequently,
please contact your dealer.
1 Vbat_OV
Battery over voltage.
Check whether the battery
voltage setting of the
charger is consistent with
the battery configuration.
Change battery voltage of
the charger, or change
battery configuration.
If it happens frequently,
please contact your dealer.
2 Vbat_OV_HD
3 Buck_Short Cut Battery short circuit.
Check battery wiring. And
charger will return to normal
operation after the failure
disappears.
If no, please contact your
dealer.
4 I_Buck1_OC
Buck1 of charger over
current.
Check whether the
maximum charging current
is over range.
Check whether the charger
model setting is correct.
If the settings are correct,
please contact your dealer.
5 I_Buck2_OC Buck2 of charger over
current.