Energier Apollo User Manual
38
Items
Floating Voltage
Temperature
compensation
coefficient
Auxiliary out1
27.2VDC
50.8VDC
27.2VDC
54.4VDC
-4mV/℃/cell
To configure temperature
compensation coefficient of lead
acid battery to avoid overcharging
To configure trigger source
of auxiliary relay 1
Descriptions
To configure suitable floating
voltage for battery bank
27.0VDC
54.0VDC
Selectable options default setting
-6~0mV/℃/cell
AGS; Battery Low; Fan running;
Inverter Fault; Output short;
Over charge; Overload;
Over temperature
Battery Low
Auxiliary out2
To configure trigger source
of auxiliary relay 2
To configure over charge
protection threshold
Enable or disable the alarm of
AC input voltage abnormal
Enable, disable Enable
AGS; Battery Low; Fan running;
Inverter Fault; Output short;
Over charge; Overload; Over
temperature; AC input connect
Battery Low
Inverter to grid
threshold
20.0~32.0VDC/
40.0~64.0VDC
“Inverter to grid” threshold in
solar mode. Grid provides power
to the AC loads only when
battery voltage drops to the value
21.0VDC/
42.0VDC
Grid to inverter
threshold
Bulk finished/
Absorption finished
“Grid to inverter” threshold in solar
mode. Energier Apollo will be
back to invert mode when battery
voltage increases to the value or
end of bulk/absorption charging
Bulk finished
Over charge
protection
AC input voltage
abnormal alarm
28.0~32.0VDC/
56.0~64.0VDC
32.0VDC/
64.0VDC
LFP
Flooded
Lead-
carbon
23.0~32.0VDC /
46.0~64.0VDC
23.0~32.0VDC /
46.0~64.0VDC
23.0~32.0VDC /
46.0~64.0VDC