P6. Optimise Off
1. Press or to select program 6:
Optimum Off periods will, when selected, switch off a boiler / heating system
earlier than the programmed off time.
At 15ºC external temperature the full optimum off period will occur and the
boilers will switch off early. At 0ºC external temperature there will be no
optimum off and the boilers will switch off at the normal programmed time. At
external temperatures between 0ºC and 15ºC the system will calculate the
required off time.
If Optimum Off is not required then set to 000 mins.
2. Press to display:
3. Press or to set the required number of minutes.
4.
Press to confirm program changes and return to main menu.
RETURN SELECT
6 OPTIMISE OFF
CURRENT 000 MINS
P
PROGRAM
UP/DN TO CHANGE
CURRENT 000 MINS
RETURN SELECT
E
ENTER