English 
 34 
Troubleshooting 
In general, all of the settings in the menus PAR and MEN and the terminals should be checked if 
there is an error. 
Malfunction, but “realistic” temperatures: 
  Check the program number. 
  Check the thresholds for on/off and the set differential temperatures. Have the thermostat and 
differential thresholds been reached? 
  Were the settings in the submenus (MEN) changed? 
  Can the output be switched on/off in manual mode? - If endurance runs and standstill at the 
output produce an appropriate reaction, the unit is definitely not broken. 
  Are all of the sensors connected to the right terminals? - Heat the sensor using a lighter and 
check the display. 
Incorrect temperature displayed:  
  If a value such as -999 is displayed when a sensor short-circuits or 999 if there is an interruption, 
the cause may not be a material or terminal error. Are the correct sensor types (KTY or PT1000) 
selected under the menu MEN/ SENSOR? The factory settings have all inputs set to PT (1000). 
  The sensor can also be checked without a measuring device simply by changing the part that is 
probably defective with one that works at the strip terminal and checking the display. The 
resistance measured with an ohmmeter should have the following value according to the 
temperature: 
Temp. [°C]  0  10 20 25 30 40 50 60 70 80 90 100
R (Pt1000) [Ω]  1000 1039 1078 1097 1117 1155 1194 1232 1271 1309 1347 1385
R (KTY) [Ω]  1630 1772 1922 2000 2080 2245 2417 2597 2785 2980 3182 3392
 
The settings of the parameters and menu functions ex works can be restored at any time 
using the down key (entry) when plugging the unit in. If this occurs, WELOAD will appear in 
the display for three seconds. 
 
If the unit does not run when it has power, the quick-blow fuse 3.15A that protects the 
control system and the output should be checked and exchanged if necessary. 
 
As the programs are constantly being revised and improved, there may be a difference in the 
numbering of the sensors, pumps, and programs. Only the instruction manual provided with the 
device delivered applies (identical serial number). The program version of the manual must 
correspond to the one for the device. 
If the control system malfunctions despite these checks as described above, please contact your 
retailer or the manufacturer directly. The cause of the error can only be determined if the table of 
settings has been completely filled in along with a description of the error. If possible, also include 
a hydraulic diagram of the system.