Group 15: PLC Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
15-27
AS4 Current Value
0~65534 (Note4)
0
15-28
MD1 Current
Value
0~65534 (Note4)
0
15-29
MD2 Current
Value
0~65534 (Note4)
0
15-30
MD3 Current
Value
0~65534 (Note4)
0
15-31
MD4 Current
Value
0~65534 (Note4)
0
15-32
TD Current Value
0~65534 (Note4)
0
Group 16: LCD Function Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
16-00
Main Screen
Monitoring
5~82
(Note4)
when using
LCD to
operate, the
monitored item
displays in the
first line.
(default is
frequency
command)
16 *1
16-01
Sub-Screen
Monitoring 1
5~82
(Note4)
when using
LCD to
operate, the
monitored item
displays in the
second line.
(default is
output
frequency)
17 *1
16-02
Sub-Screen
Monitoring 2
5~82
(Note4)
when using
LCD to
operate, the
monitored item
displays in the
third line.
(default is
output current)
18 *1
16-03 Display Unit
0~39999
Determine the
display way
and unit of
frequency
command
0
0: Frequency
display unit is
0.01Hz
1: Frequency
display unit is
0.01%
2: Frequency
Group 16: LCD Function Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
display unit is
rpm.
3~39:
Reserved
40~9999:
Users specify
the format,
Input 0XXXX
represents the
display of
XXXX at 100%.
10001~19999:
Users specify
the format;
Input 1XXXX
represents the
display of
XXX.X at
100%.
20001~29999:
Users specify
the format,
Input 2XXXX
represents the
display of
XX.XX at
100%.
30001~39999:
Users specify
the format,
Input 3XXXX
represents the
display of
X.XXX at
100%.
16-04
Engineering
Unit
0: without
using
engineering
unit
0
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m