EasyManua.ls Logo

TECO A510s Series - Page 39

TECO A510s Series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Group 16: LCD Function Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
16-05 LCD Backlight 0~7 5 *1
16-06 Reserved
16-07
Copy Function
Selection
0: Do not copy
parameters
0
1: Read
inverter
parameters and
save to the
operator.
2: Write the
operator
parameters to
inverter.
3: Compare
parameters of
inverter and
operator.
16-08
Selection of
Allowing
Reading
0: Do not allow
to read inverter
parameters and
save to the
operator.
0
1: Allow to read
inverter
parameters and
save to the
operator.
16-09
Selection of
Operator
Removed
(LCD)
0: Keep
operating
when LCD
operator is
removed.
0 *1
1: Display fault
when LCD
operator is
removed
Group 17: Automatic Tuning Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
17-00
Mode Selection
of Automatic
Tuning*
0: Rotation
Auto-tuning
VF:2
VF+PG
:2
SLV:6
SV:6
SLV2:6
1: Static Auto-
tuning
2: Stator
Resistance
Measurement
3: Reserved
4: Loop Tuning
Group 17: Automatic Tuning Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
5: Rotation
Auto-tuning
Combination
(item: 4+2+0)
6: Static Auto-
tuning
Combination
(item: 4+2+1)
17-01
Motor Rated
Output Power
0.00~600.00 KVA
17-02
Motor Rated
Current
0.1~1200.0 KVA
17-03
Motor Rated
Voltage
200V: 50.0~240.0
-
400V: 100.0~480.0
-
575V:150.0~670.0
-
690V: 180.0~804.0
-
17-04
Motor Rated
Frequency
4.8~599.0
50.0/
60.0
17-05
Motor Rated
Speed
0~24000 KVA
17-06
Pole Number of
Motor
2~16 (Even) 4
17-07
PG Pulse
Number
0~60000 1024
17-08
Motor no-load
Voltage
200V: 50~240
-
400V: 100~480
575V: 420~600
690V: 504~720
17-09
Motor
Excitation
Current
0.01~600.00 -
ï¿­1
17-10
Automatic
Tuning Start
0: Disable
0
1: Enable
17-11
Error History of
Automatic
Tuning
0: No error
0
1: Motor data
error
2: Stator
resistance
tuning error
3: Leakage
induction
tuning error
4: Rotor
resistance
tuning error
5: Mutual
induction
tuning error
6: Encoder
error
7: DT Error
8: Motor’s
acceleration
error
9: Warning
17-12
Proportion of
Motor Leakage
0.1~15.0 3.4