F_10: Start / Stop Control = 0 : Keypad
=1:Terminal (TM2)
NOTE: When F_10 = 1 (Terminal Control), emergency stop on the Keypad is enabled.
To avoid injuries to personnel or equipment damage when F_10 = 1, please refer to the descriptions of F_23/24 (Momentary
power loss ride-through and number of auto restart attempts).
Priority of selections for JOG, multi-function, and keypad/external frequencies
F_11: Frequency Control = 0 : Keypad
=1:Analog Speed Pot Terminal (TM2) (0 ~ 10V / 0-20mA)
=2:Analog Speed Pot Terminal (TM2) (4-20mA)
NOTE 1:
If the jog when start/stop control is set to keypad run
or SP1 frequency is switched on, the frequency is set
by SP1 speed and the frequency set up via the ▼▲ buttons
on the keypad are disabled.Original settings will be restored
after the SP1 connection or jog input is removed.
NOTE 2:
During the contact closure of the jog function, the keypad
control remains inactive until the jog contact connection
is reopened.