26
(5): 15-6 Reset the factory setting 1110: Reset the 50Hz factory setting
1111: Reset the 60Hz factory setting
(6):15-7 Parameter locking password 0000~0999
Establish the password procedure:
15-7 = 888 (establish the password command) 15-7 = establish the password
(establish the password that the customer appoints) Completion
Unlock the parameter:
When the parameter is locked, only 15-7 can be used, if want to unlock the parameter,
input the primitive password of establishing on 15-7, other parameters can make an
modification after unlocking.
Remove the password by force:
When forget the primitive password that establishes, remove the settlement of the
primitive password with this procedure, when need to do the password to lock, please
operate it in accordance with above-mentioned "Establish the password procedure".
15-7 = 123 (remove the password command 1)
ٛ
15-7 = 999 (remove the password
command 2) The original password has already been removed.
Note:
1. When inverter needs to establish a new password, please input the primitive
password first to unlock parameter, can just use “Establish the password
procedure” to establish the new password.
2. If the inverter has password of establishing, the inverter will lock the parameter
automatically after power on.
3. Please avoid the value of 15-7 to use 123, 888, 999, 000.
(7):15-8 Copy Unit 0000: Disable
0001: Inverter to Copy Unit
0002: Copy Unit to Inverter
0003: Verify
1.) 15-8=0000: Disable.
2.) 15-8=0001: Copy the inverter parameters to module.
3.) 15-8=0002: Copy the module parameters to inverter.
4.) 15-8=0003: Copy the parameters to inverter or module to mutually verify the
parameters.
Note: The copy function is available for the models with same capacity.