EasyManua.ls Logo

TECO SG2-12HT-D - Page 121

TECO SG2-12HT-D
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Relay Ladder Logic Programming 113
-
MU mode4: Read Coils
Set parameter , address, to be constant:
Function parameter display:
Set a constant address 20 ( here is a Hex number)
Data length is a constant value: 10 in Hex format
When enable the MU function, the sending out Modbus
command will be:
01 01 00 20 00 10 CRC16;
Received response from slaver:
01 01 02 data1-1 data1-2 CRC16;
Saving data to DRE0:
DRE0 = data1-1 + data1-2
Set parameter , address, refer to data register DR:
Function parameter display:
Set DR03=0001 for address
Set DR04=0015 (hex: 000F) for data length;
(means how many coil’s state will be read)
When enable the MU function, the sending out Modbus
command will be:
01 01 00 01 00 0F CRC16;
Received response from slaver:
01 01 02 data1-1 data1-2 CRC16;
Saving data to DRE0:
DRE0 = data1-1 + data1-2
the max length of data is 400.
PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

Table of Contents

Related product manuals