EasyManua.ls Logo

TECO SG2-12HT-D - Real Time Clock (RTC) Instructions

TECO SG2-12HT-D
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Relay Ladder Logic Programming 90
-
7BReal Time Clock (RTC) Instructions
The SG2 smart relay includes 31 RTC coils that can be used throughout a program.
Each RTC instruction has a choice of 5 operation modes, and has 10 parameters for proper
configuration. The initial clock/calendar setting for each connected SG2 is set using the
Operation»RTC Set menu selection from the SG2 Client software.
RTC Mode 0 (Internal Coil)
Mode 0 RTC (Internal Coil) used as internal auxiliary coils. No preset value. In the example below shows the
relationship among the numbered block diagram for a Mode 0 RTC, the ladder diagram view, and the software Edit
Contact/Coil dialog box.
Symbol Description
Input the first week to RTC
Input the second week to RTC
RTC mode 0~2, 0: internal coil 1:daily, 2:consecutive day
s
RTC displays the hour of present time.
RTC displays the minute of present time
Set RTC hour ON
Set RTC Minute ON
Set RTC Hour OFF
Set RTC Minute OFF
RTC Coil Number (R01~R1F Total: 31 RTC)