Chapter 3 Program Tools     59 
SG2 system error 
After power on, SG2 keep detecting the running state. Once system error occurred, the error code will display on 
LCD.    At the same time, SG2 will stop or just give error-warning base on the error type. Error types are show in the 
table below: 
Error code  Explain  Error action  Why and    How 
ROM ERROR  System ROM/Flash memory check 
error 
SG2 STOP  If the version of the firmware is older 
than 3.4, update to 3.4 or newer; then 
if the error occurs again, contact with 
suppliers 
Vpd ERROR  Power down circuits check error  SG2 STOP  Voltage is too low; apply the 
appropriate voltage 
PROG ERROR  Ladder / FBD code invalid in 
EEPROM.  
SG2 STOP  Download the user program and try 
again. 
LOGIC ERROR  FBD code logic check error  SG2 STOP  There is same logic error in the user 
program, modify it and try again. 
EXT. ERROR  Expansion I/O error (When disable I/O 
alarm in “SET” of the main function, 
The alarm cannot appear.) 
SG2 STOP  Extend module set number is not same 
with the actual number, check the 
system set. 
COMM ERROR  RS485 type communication error    Warning only  V type module communication error, 
check the COMM protocol. 
RTC ERROR  RTC check or work error  Warning only  Contact with suppliers. 
EMPTY PACK  Memory pack is empty, when reading 
from the memory pack. 
Warning only  No memory pack or there is no user 
program in the memory pack, check 
the memory pack. 
MEM.ERROR  Memory packs check error, when 
writing to the memory pack. 
Warning only  Memory pack is broken or no memory 
pack, check or change it. 
T.ERROR  The type is not matching when reading 
program from the memory pack. 
Warning only  The type of the user program in the 
memory pack does not match with 
current one. 
 