EasyManua.ls Logo

TECO SG2-12HT-D - K Type Indicator Light

TECO SG2-12HT-D
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2 Installation 20
The power supply and the I/O supply should share the same power source. Only short circuit the first and the last
module.
When I/O link, the net can connect 8 products in max. (ID: 0-7).
When Remote I/O is available, it only can connect 2 products max (Master & Slaver).
More information about RS485 Model communication to see “Chapter 7 20 Points RS485 type Models
Instruction”.
-1A quick-blowing fuse, circuit-breaker or circuit protector
-Surge absorber (43V DC)
-Surge absorber (Input 24VAC:43V; Input 100~240VAC:430V AC)
-Fuse, circuit-breaker or circuit protector
-Inductive load
-Comply with standard: EIA RS-485.
K type Indicator Light
There is an indicator light to indicate the status of SG2 (K type) smart, and the below table shows the
relationship between the light and the SG2 status.
State of light Description
Power up, SG2 is stopping
Flicker slow(1Hz), SG2 is running
Flicker quick(5Hz), SG2 is under failure status
Flash error
Illogicality in user program
Expansion model error
RTC error
PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

Table of Contents

Related product manuals