Chapter 6 FBD Block  Diagram Programming    139 
HMI 
The SG2 smart relay includes a total of 31 HMI instructions that can be used throughout a program. Each HMI instruction 
can be configured to display information on the SG2 16×4 character LCD in text, numeric, or bit format for items such as 
current value and preset value for functions, Input/Output bit status, and text. There are three kinds of text in HMI. They 
are Multi Language, Chinese (fixed) and Chinese (edit). 
※ Only the coils, function blocks and analog value which used in the program can be set in HMI to display status, 
preset value and current value. 
 
Each HMI instruction has a choice of 2 operation modes. 
Mode1, display mode when pressing key “SEL” can display HMI preset. 
Mode2, no display mode when pressing key “SEL” can’t display HMI preset. Displays preset only be enabled.   
 
Example: H01 controlled by M01, and setting H01 mode1, display M01 status, preset value and current value for 
block B001 (Timer T01), current value for block B002 (Counter C01). 
 
 
FBD output coil display 
M01: enable input coil 
Press “OK” button into 
function display 
Press “SEL” , “↑ ↓” and “OK” to 
edit HMI mode 
   
 
 
HMI display and keypad function, same as ladder mode HMI function. 
Press “SEL” button when 
stopping 
Enabled display when 
running 
Press “SEL” , “↑ ↓” and “OK” to 
edit preset value, coil status 
 
 
 
※ More information about HMI/TEXT to see:   
Chapter 3: Program Tools—Ladder Logic Programming Environment —HMI/TEXT. 