Chapter 6 FBD Block Diagram Programming 185
MU mode2: Write single register
Setting communication address is constant:
Mode2 FBD display Parameter display
Enable Input
Slaver ID
Register address
Parameter
Source data address
Setting communication address is data register DR:
Mode2 FBD display Parameter display
Enable Input
Slaver ID
Register address
Parameter
Source data address
Address is constant 0003,
Setting data DRE0=1234 (hex: 04D2),
Send data:
01 06 00 03 04 D2 CRC16;
Received response from slave1:
01 06 00 03 04 D2 CRC16
Setting address DR03=0001,
Setting data DRE0=1234 (hex: 04D2),
Send data:
01 06 00 01 04 D2 CRC16;
Received response from slave1:
01 06 00 01 04 D2 CRC16;