Chapter 9 Expansion Module 226
When the preset value in “Analog Output Set” screen is a constant, this value will be stored in DR register,
(DRD4~DRD7) and the AQ value equals to (DRx/4.095). For example, CH1 is configured as mode 1, set a
constant value, 4000, then the value of AQ01 will be 977, and HMI displays 9.77V.
Once the preset value refers to other variable, its value is also stored in DR register, (DRD4~DRD7), but it will
be equal to AQx * 4.095. (DRx=AQx*4.095).
More information about expansion analog input to see: Chapter 5 Relay Ladder Logic Programming –AQ
(Analog output).
Wiring
Voltage output Current output