APPENDIX E - SensoIRIS Sounders Consumption
Tables: Calculation of the consumption of SensoIRIS sounders.
To calculate the total consumption of the sounders in the loop and to define the proper sound level, you can use the
Table a below, as fill in the number of the used sounders according their type.
Table 1 for calculation of the total consumption of the sounders in the loop with defined sound level and set ALARM
and/or EVACUATE TONE type 27 (see item 3.5.4 Sounders Mode):
Sounder
Number
HIGH
Sound Level
LOW
Sound Level
Total consumption, mA
(HIGH + LOW)
WS
____ x 16,5mA
____ x 5mA
WS IS
___ x 16,5mA
___ x 5mA
WSOU
____ x 16,5mA
____ x 5mA
WSOU IS
____ x 16,5mA
____ x 5mA
WSST
____ x 22mA
____ x 12mA
WSST IS
____ x 22mA
____ x 12mA
BSOU
____ x 10mA
____ x 3mA
BSOU IS
____ x 10mA
____ x 3mA
BSST
____ x 10mA
____ x 3mA
BSST IS
____ x 10mA
____ x 3mA
Consumption of the sounders in the loop:
Table 2 for calculation of the total consumption of the sounders in the loop with defined sound level and set ALARM
and/or EVACUATE TONE other type sound (see item 3.5.4 Sounders Mode):
Sounder
Number
HIGH
Sound Level
LOW
Sound Level
Total consumption, mA
(HIGH + LOW)
WS
____x 10mA
____ x 4mA
WS IS
___ x 10mA
___ x 4mA
WSOU
____ x 10mA
____ x 4mA
WSOU IS
____ x 10mA
____ x 4mA
WSST
____ x 16,5mA
____ x 11mA
WSST IS
____ x 16,5mA
____ x 11mA
BSOU
____ x 10mA
____ x 3mA
BSOU IS
____ x 10mA
____ x 3mA
BSST
____ x 10mA
____ x 3mA
BSST IS
____ x 10mA
____ x 3mA
Consumption of the sounders in the loop: