TEMPMASTER
12
FORM TPM3-EG1 (518)
ROOF CURBS
Full Perimeter Roof Curbs – This option includes a knock-down 14-inch high roof curb
for use with wood nailer (by others). Roof curb supports the entire perimeter of the unit.
Partial Perimeter Roof Curbs – This option includes a knock-down 14-inch high roof
curb for use with wood nailer (by others). Roof curb supports the air handling section with
a separate support under the condenser end.
CABINET FEATURES AND OPTIONS
Double-Wall Access Doors - Full-sized access doors provide easy access into the unit
for routine maintenance and inspection. Solid wall liners encase insulation and prevent
damage and erosion into the airstream.
Diffuser Section – An optional diffuser section is available downstream of the supply
fan in the extended discharge plenum cabinet option. The diffuser section distributes the
airflow from the fan evenly across the downstream filter bank to optimize filter life and
effectiveness. The diffuser design is optimized to provide uniform flow at minimal airside
pressure loss.
Downstream Final Filter Rack – A 90–95% efficient MERV 14, 12-inch rigid filter rack
and filters shall be provided downstream of the supply fan and diffuser segment for hospi-
tal applications. A magnahelic pressure gauge is included and visible from the outside of
the unit for servicing and code compliance.
Blank Section – A blank section shall be provided downstream of the supply fan and dif-
fuser section.
ACCESSORIES
Filter Switch – An optional dirty filter alarm can be provided that will provide an alarm
when the filters require cleaning.
Magnahelic Filter Pressure Gauge – On units equipped with downstream filtration, a
magnahelic filter gauge is included and visible on the exterior of the unit. The filter gauge
measures the air pressure drop for through the rigid filter bank to indicate when replace-
ment is required.
Features and Benefits (Cont'd)