Premier 48, 88, 168 & 640 Installation Manual Installation
INS176 21
Panel Outputs 1 - 5
The control panel has five programmable outputs, which can
be used to drive auxiliary devices such as LED’s, sounders or
relays etc. (see page 60 for details). The table below shows
the electrical characteristics for each output:
No Max Current Type
1 1A Switched -ve
2 1A Switched -ve
3 * 1A Switched +ve
4 * 1A Switched +ve
5 * 3A Relay
* Premier 88, 168 and 640 only
Wiring Outputs
The diagram below shows some typical wiring examples:
For details on testing outputs, see page 92
Digicom Outputs 1 - 8
The control panel has eight programmable outputs, which
can be used for connecting to a stand-alone communicator
(see page 61 for details). The table below shows the electrical
characteristics for each output:
Terminal Max Current Operation
1 100mA Switched 0V
2 100mA Switched 0V
3 100mA Switched 0V
4 100mA Switched 0V
5 100mA Switched 0V
6 100mA Switched 0V
7 100mA Switched 0V
8 100mA Switched 0V
L/M N/A 12V applied = Line Fault *
R/R N/A 0V applied to reset
DC+ N/A +12V Power (unfused)
DC- N/A 0V Power
* Control Panel Line Fault Input (L/M)
In accordance with BSIA form 175, the line fault input on the
control can detect a single or a dual line fault for use with the
ATS Remote Test output type
Wiring a Stand Alone Communicator
The diagram below shows a typical wiring example:
Control
Panel
Power
1
3
4
5
6
7
8
12V
0V
Stand Alone
Communicator
C
DC +
L / M
R / R
DC -
1
3
4
5
6
7
8
Channel Inputs
Programmed
as Positive
Removed
Line Fault
Digicom
Outputs
For details on testing the digicom outputs, see page 92