Premier 48, 88, 168 & 640 Installation Manual Programming the Control Panel
INS176 79
No Zone Type Event Reporting Group Contact ID SIA
11 Auxiliary Alarm Alarm Tamper 150 UA
Alarm Restore Restore 150 UH
Omit Omit/Reinstate 572 UB
Reinstate Omit/Reinstate 572 UU
12 24Hr Tamper Alarm Alarm Tamper 137 TA
Alarm Restore Restore 137 TR
Omit Omit/Reinstate 572 TB
Reinstate Omit/Reinstate 572 TU
13 Exit Terminator Alarm Open/Close --- --
Alarm Restore Open/Close --- --
Omit Omit/Reinstate 570 UB
Reinstate Omit/Reinstate 570 UU
14 Keyswitch - Momentary Alarm Open/Close 409 OP
Alarm Restore Open/Close 409 CL
Omit Omit/Reinstate 570 UB
Reinstate Omit/Reinstate 570 UU
15 Keyswitch - Latching Alarm Open/Close 409 OP
Alarm Restore Open/Close 409 CL
Omit Omit/Reinstate 570 UB
Reinstate Omit/Reinstate 570 UU
16 Security Key Alarm Open/Close 421 DK
Alarm Restore Open/Close 421 DG
Omit Omit/Reinstate 570 UB
Reinstate Omit/Reinstate 570 UU
17 Omit Key Alarm Omit/Reinstate --- --
Alarm Restore Omit/Reinstate --- --
Omit Omit/Reinstate 570 UB
Reinstate Omit/Reinstate 570 UU
Non-Zone Event Types
The default Non-Zone Event codes are as follows:
No Type Event Reporting Group Contact ID SIA ID
20 Keypad Medical Alarm Priority Alarm 100 MA Keypad No *
Restore Restore 100 MH Keypad No *
21 Keypad Fire Alarm Priority Alarm 115 FA Keypad No *
Restore Restore 115 FH Keypad No *
22 Keypad Audible PA Alarm Priority Alarm 120 PA Keypad No *
Restore Restore 120 PH Keypad No *
23 Keypad Silent PA Alarm Priority Alarm 122 PA Keypad No *
Restore Restore 122 PH Keypad No *
24 Duress Code Alarm Alarm Priority Alarm 121 HA User No
Restore Restore - 122 HH User No
25 Alarm Active Alarm Not Reported - - -
Restore Not Reported - - -
26 Bell Active Alarm Not Reported - - -
Restore Not Reported - - -
27 Zones Locked Out Alarm Alarm 130 BA Zone No
Restore Not Reported - - -
28 Verified Cross Zone Alarm Alarm Alarm 130 BV 00
Restore Not Reported - - -
29 User Code Alarm Not Reported - - User No
Restore Not Reported - - -