9 Alarms
If faults occur in the heating system, it is possible to fix some of them by
following these instructions.
Display
Description
Solution
Alarm active-
indicated next to the sign
for alarm
Cancel the alarm can be executed
by pressing the button 4 .
After that, the display lists FINAL
CLEANING lasting 4 minutes. After
that we can restart the boiler if we
solve the problem.
NO IGNITION
Failed ignition.
No pellets in the silo - fill the
pellets in a silo
Dosage spiral empty - initial filling
A foreign object stuck dosage
spiral - clean
Poor quality pellets (wet pellet,
long pellets, dust into pellets) -
change the type of pellets
Pellet igniter is defective - replace
it
Contact Service
Restart the boiler.
NO PELET
During operation of the
boiler, flue gas
temperature has
decreased below the
permitted values
No pellets in the silo - fill the
pellets in a silo
Dosage spiral empty - initial filling
A foreign object stuck dosage
spiral - clean
Poor quality pellets (wet pellet,
long pellets, dust into pellets) -
change the type of pellets
Call service
SMOKE PROBE
Flue gas temperature
sensor is defective or not
connected.
Boiler lists alarm is active
and goes off.
Call service
WATER PROBE
Water temperature
sensor is faulty or not
connected
Boiler lists alarm is active
and goes off.
Call service
HOT FUMI
Flue gas temperature is
above the allowed (250 °
C). Boiler lists alarm is
active and goes off.
The boiler has not been cleaned,
smoke sensor is dirty.
Clean boiler and restart the
ignition.
Excessive amounts of feed pellets.