174
174
NC2 0 - Manual - 01 - 2015
APPENDIX
Residual overcurrent 50N/51N - Extremely inverse time curve (IEC 60255-3/BS142 type C)
F_51-IECC-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
IE /IE>inv
0.01
0.1
1
10
100
1000
10000
100000
t [s]
tE>
inv
= 10 s
tE>
inv
= 60 s
tE>
inv
= 5 s
tE>
inv
= 1 s
tE>
inv
= 0.5 stE>
inv
= 0.2 stE>
inv
= 0.02 s tE>
inv
= 0.1 s
t =
t
E
>
inv
·
[(I
EC
/I
E
>
inv
)
2
-1]
80
Note: match of operating and setting time takes place when I
EC
/I
E
>
inv
= 9