EasyManuals Logo

Thytronic NC20 User Manual

Thytronic NC20
227 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #179 background imageLoading...
Page #179 background image
179
NC2 0 - Manual - 01 - 2015
APPENDIX
Phase overcurrent 50/51 RMS - Moderately inverse time curve (ANSI/IEEE type MI)
F_51-ANSIMI-Char.ai
1.1
2 3 4 5 6 7 8 9 10 20
I
RMS
/I>
inv
0.01
0.1
1
10
100
1000
10000
t [s]
t>
inv
= 10 s
t>
inv
= 60 s
t>
inv
= 5 s
t>
inv
= 1 s
t>
inv
= 0.02 s
t>
inv
= 0.2 s
t>
inv
= 0.1 s
t>
inv
= 0.5 s
t =
t>
inv
·
[(I
RMS
/I>
inv
)
0.02
-1]
0.01
+ 0.023
Note: match of operating and setting time takes place when I
RMS
/I>
inv
= 1.664

Table of Contents