EasyManuals Logo

Thytronic NC20 User Manual

Thytronic NC20
227 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
63
NC2 0 - Manual - 01 - 2015
FUNCTION CHARACTERISTICS
Neutral unbalance current - 46N
Preface
One alarm and two operation thresholds, independently adjustable (I
N>AL
, I
N>
, I
N>>
) with adjustable
operating times (t
N>AL
, t
N>
, t
N>>
).
The fi rst one is based on defi nite time characteristic.
The I
N
> operation threshold may be programmed with defi nite or inverse time according the IEC and
ANSI/IEEE standard; the second thresholds (I
N
>>) is based on defi nite time characteristic.
The fi rst alarm threshold may be inhibited by start of the operation thresholds ( I
N
>, I
N
>>); similarly
the fi rst threshold trip may be inhibited by start of the second threshold (I
N
>>).
Operation and settings
The unbalance current I
N
is used with:
Fundamental component of the neutral unbalance current measured on the double star connection
as module.
Displacement of the unbalance current I
N
, positive for lagging current compared with I
L1
current
φ
N
=(I
N
- I
L1
) as phase displacement.
To compensate the inherent unbalance in a un-faulted three phase capacitor bank, a suitable manual
or automatic adjustment is provided.
The user may adjust the compensation values (I
C
, φ
C
) by setting I
C
= I
N
and φ
C
= φ
N
, where the neutral
current when no fault are present on-duty bank capacitors (I
N
, φ
N
) are measured by relay.
The compensated imbalance current phasor is calculated by protection relay by the vector dif-
ference I
NC
= I
N
- I
C
The user can check the current imbalance compensation by detecting the measures (I
NC
module
and φ
C
phase) for the current imbalance compensated phasor I
NC
available inside the Read \ Mea-
sures menu.
The relay internally measures the real unbalanced current when fault are present:
I
NC
= I
N
- I
C
(module and phase displacement).
The compensation parameters are adjustable inside the Set \ Compensation- 46N menu.
The compensation may be performed:
Manually by means the Manual compensation command; the setting I
C
and Phi
C
parameter are
entered
Automatically by means the Automatic compensation command; the calculated I
C
and Phi
C
pa-
rameter are used. This command is active only with user level 1 when the measured currents are
inside the operating fi eld; the upshot of the command is shown by means the ACE fl ag. The used
parameters can be read inside the Read \ Measures \ Calculated menu.
If the unbalance current I
NC
exceeds the setting threshold a start is issued. After expiry of the as-
sociated operate time a trip command is issued; if instead the current drops below the threshold, the
element is restored.
The fi rst threshold (I
N>
) may be programmed with defi nite or inverse time according the following
characteristic curves:
Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t
N
>
inv
/ [(I
NC
/I
N
>
inv
)
0.02
- 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t
N
>
inv
/ [(I
NC
/I
N
>
inv
) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t
N
>
inv
/ [(I
NC
/I
N
>
inv
)
2
- 1]
Moderately Inverse (ANSI/IEEE type MI): t = t
N
>
inv
· {0.01 / [(I
NC
/I
N
>
inv
)
0.02
- 1] + 0.023}
Very Inverse (ANSI/IEEE type VI): t = t
N
>
inv
· {3.922 / [(I
NC
/I
N
>
inv
)
2
- 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI): t = t
N
>
inv
· {5.64 / [(I
NC
/I
N
>
inv
)
2
- 1] + 0.024}
Where:
t: operate time
I
NC
: compensated unbalance current
I
N
>
inv
: threshold setting
t>
inv
: operate time setting
The alarm threshold (I>
AL
) has defi nite time characteristic.
For all inverse time characteristics, following data applies:
Asymptotic reference value (minimum pickup value): 1.1 I
N
>
inv
t-int-F46N.ai
I
NC
I
N
> I
N
>>
t
N
>
AL
t
N
>
t
N
>>
I
N
>
AL
t
TRIP
General operation time characteristic for the neutral unbalance elements - 46N
t-int-F46N.ai
I
NC
I
N
> I
N
>>
t
N
>
AL
t
N
>
t
N
>>
I
N
>
AL
t
T
RIPTRIP
General operation time characteristic for the neutral unbalance elements - 46N

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic NC20 and is the answer not in the manual?

Thytronic NC20 Specifications

General IconGeneral
BrandThytronic
ModelNC20
CategoryPower distribution unit
LanguageEnglish

Related product manuals